Update a FloraPulse SDI-12 sensor box over its own sensor wires — from this page, with the FloraPulse SDI-12 uploader. Nothing to install.
FloraPulse SDI-12 boxes shipped from October 2026 onward carry a built-in bus bootloader: they accept new firmware through the same two wires they measure on. This page sends the current production firmware to your box and verifies it end to end. Boxes shipped earlier do not have the bootloader and cannot be updated this way — if the tool reports that, nothing was changed.
Never update a box while it is connected to a logger. A METER ZL6 powers the sensor for about one second per minute — the update needs continuous power for its whole run: a minute or two on a recent box, up to 15 minutes on an older one. Update on the uploader, then put the box back on the logger.
Keep this tab in the foreground and everything plugged in until it says CONFIRMED. A new image that is never confirmed is automatically rolled back by the box's bootloader — that is a safety feature, not a fault. If the tool ends with anything other than CONFIRMED, leave everything connected and run it again.
| # | Address | Box | Was | Now | Result | Ship check |
|---|
This tool needs Chrome or Edge on a computer (it talks to the uploader through Web Serial, which this browser does not provide). The page is otherwise just instructions — open it again from a desktop browser.
It runs by itself. Once this browser knows the uploader (the first time you pick its port), the page connects the moment the uploader is plugged in — or at once, if it already is — and then watches the wires: clip a box and its update starts; when it says CONFIRMED, unclip it, clip the next box, and that one starts too. Nothing to click between boxes. A box it has just finished is left alone until it is unclipped, so nothing is ever sent twice; Update box now runs whatever is clipped on regardless. The one time it waits for you is a box that already runs newer firmware than this page installs — it will not roll a box back without a click. While the page is connected it holds the uploader's port; click Disconnect to use the uploader from the calibration page or SDI12 QC.
Plugging in or connecting to the uploader restarts the box — that's normal. The update takes about a minute on a recent box and 12 to 15 minutes on an older one; the box keeps its serial number and calibration through it.
Every connect also checks the uploader's own firmware. If it is older than the current version, the page updates it first, automatically (about a minute, over the same USB cable — the uploader restarts, which restarts the box too), and then goes on to the box.
Building or fixing just the uploader? Click Flash uploader firmware — it loads the current uploader firmware onto the Arduino Nano through the Nano's own bootloader (about a minute) and touches no box. Use it for a brand-new Nano off the bench, or if an uploader ever stops responding. If the uploader is already current it says so and flashes nothing; either way the page then connects and waits for a box as usual.
You can work in another window beside it, but keep this tab showing and the laptop plugged in: the page can only keep the laptop awake while an update is running and it is on screen. The tab's title shows the progress, and when an update ends the page plays a chime and shows a desktop notification (your browser asks once, at your first click on the page, whether it may).
Several boxes? Switch to Several boxes above and clip the boxes you have, in parallel, colour to colour: boxes that already carry a number can all go on together, boxes at address 0 go on one at a time. Click Connect & find boxes — the page scans every address in about eight seconds and lists what it finds, and a lone box at 0 is given the next free number (write it on the box). Clip the next box beside the others, click Add box, and so on. A box may restart when another is clipped in; between runs that is harmless. Every box is listed, including one that needs nothing (already current, or too old to update) — it simply is not run. Boxes made together often carry the same probe name; that is expected and never a problem. When every box is on, click Start updates: they run one after another (about a minute or two each for a recent box, 12 to 15 minutes for an older one; the page shows the total beside Start updates), and each box goes back to address 0 as it finishes — unclip finished boxes whenever you like, and clip nothing new while an update is running. A box that fails stays at its number until you click Retry the failed or Reset addresses & finish. Boxes you had already given their own addresses for a logger port are updated where they sit and left at those addresses. A few boxes run from the uploader's own power; for a larger batch power them from an always-on 12 V supply such as a Campbell logger's (not a ZL6, which powers sensors only a second a minute), with the logger's own program stopped, and clip only the white and black wires.
| Result | What to do |
|---|---|
| CONFIRMED | Done. Put the box back on its logger. |
| Already current | The box already runs the latest firmware. Nothing was changed. |
| Not started | You clicked Disconnect at the check, or the uploader was unplugged. Nothing was changed. |
| No bus update | This box predates the bootloader (shipped before October 2026) and cannot be updated over the wire. Nothing was changed. |
| UNCONFIRMED | The new image is on probation. Leave the box on the uploader and run the tool again; do not put it on a logger. If it stays unconfirmed, copy the log and email us. |
| Reverted / not applied | The box protected itself and still runs its previous firmware. Safe — copy the log and email us before retrying. |
| Failed | The transfer did not complete; the box is unchanged. Check wiring and the address, then run it again. |
Email admin@florapulse.com with the box serial (on its label), what the status line said, and the copied log.